1. Carefully monitor the water temperature of your pool in the summertime. You can reduce heater usage due to warmer air temperatures

2. Minimum Clearance From Combustible Material (See Table 2 in Section 2.3.2)

3. Certified for use with: Natural Gas or Liquefied Petroleum Gas (LP Gas or Propane Gas)

Flame has yellow lazy tip.

1. Low primary air. Correct manifold pressure according to rating plate. Correct orifice size if necessary (see parts list). Clean burner ports if dirty.

Flame roll-out on start up.

1. Blocked flue. Remove blockage.
2. Pilot out of position (delayed ignition). Correct pilot position.
3. Blocked heat exchanger. Clean and correct as necessary.
4. Refractory blanket out of place. Correct or replace blanket as necessary.
5. Altered draft hood. Install factory-provided draft hood

Heater condensing.

1. Low water temperature. Flue product moisture will condense at the start-up until the heater water temperature reaches the normal operating conditions.

Heater pounding or knocking.

1. Inadequate water flow through heater. Check temperature rise between inlet and outlet heater piping. See section 7.6 for recommended range of temperature rise. If temperature rise is above the maximum recommended, increase pipe size or pump capacity or locate obstruction. Check for closed valve in system.

Heater short cycles.

1. Low water flow through heater. Increase size of pump or increase piping size.
2. Failing hi-limit switch. Check High limit switches and replace if necessary.

Hot surface igniter does not glow.

1. No power to heater. Check circuit breakers and power source.
2. Heater not grounded correctly. Check ground wire connection.
3. Broken or faulty hot surface igniter. Replace hot surface igniter.
4. Faulty ignition control. Replace ignition control.

Igniter glows, but main burners do not come on.

1. Gas valve not at “on” position. Turn knob to “on” position.
2. Hi-limit switches failed. Investigate reason for overheating and replace hi-limit switch as necessary.
3. Pressure switch failed or out of adjustment. Adjust pressure switch or replace as necessary.
4. Fusible link failed. Investigate reason for flame rollout and replace fusible link as necessary.
5. Gas valve failed. Check and replace gas valve as necessary.
6. Broken wire in thermostat circuit or defective thermostat. Check continuity through thermostat circuit with wires disconnected.

Not enough heat.

1. Inadequate gas supply. Gas meter too small. Gas line from meter to heater too small.
2. Low manifold gas pressure. Gas pressure on heater manifold, should be adjusted to 4.0"W.C. for natural gas, 9.0" W.C. for propane.
3. Heater size inadequate. Replace with heater of higher output.

Pilot is lit, but main burners will not turn on.

1. Gas valve not at “on” position. Turn knob to “on” position.
2. Hi-limit switches failed. Investigate reason for overheating and replace hi-limit switch as necessary.
3. Pressure switch failed or out of adjustment. Adjust pressure switch or replace if necessary.
4. Fusible link failed. Investigate reason for flame rollout and replace fusible link if necessary.
5. Gas valve failed. Check and replace gas valve as necessary.
6. Broken wire in thermostat circuit or defective thermostat. Check for continuity of the thermostat with wires disconnected.
7. Heater wired incorrectly. Check heater wiring against wiring diagram in heater, correct as necessary.

Pilot outage.

1. Inlet gas pressure may be too low. Consult gas utility company. Inlet gas pressure to heater should be 5.5" to 10.0" water column on natural gas. 10.0" to 14.0" on propane gas.
2. Inlet gas pressure too high causing an unstable blowing pilot. Pressure should be regulated within limits shown above.
3. Weak or defective thermocouple. Replace thermocouple.
4. Damaged pilot or thermocouple. Replace.
5. Dirty pilot. Blow dust or lint out of pilot.
6. Plugged or undersized pilot orifice. Clean or replace pilot orifice.

Pressure relief valve opens.

1. Restriction in water flow system at or downstream of heater.
2. Check for proper operation of all valves, bypass valve and any equipment between pool or spa and heater outlet.

Spillage at draft hood.

1. Cold chimney. Allow heater to operate 5 minutes to create draft action.
2. Vent pipe pitches down to chimney. Reinstall vent pipe to pitch up from heater to chimney.
3. Blocked chimney. Remove blockage.
4. Draft hood altered. Install factory-provided draft hood.
5. Prefabricated chimney with incorrect cap. Install U.L. listed vent cap.

Automatic Pool Cleaners

Jandy Lite 2 Parts List

Launch our online catalog viewer to review breakout diagrams and part numbers.

learn more
FileDescriptionSize
H0275300.pdfJandy Lite2 LD Heater I/O Manual2.03 MB
H0275000.PDFJandy LD/LJ Side Wall Vent Kit Installation Instructions886.91 KB
L0858.pdfJandy Lite2 LJ Troubleshooting Guide232.17 KB
L0755.pdfJandy Lite2 Low Nox Troubleshooting Guide93.11 KB
H0242400.pdfJandy Lite2 LD-LowNOx Heater I/O Manual903.03 KB
H0208700G.pdfJandy Lite2 Model LG Heater I/O Manual1.07 MB
H0264600.pdfJandy Lite2 LG Heater I/O Manual1.79 MB
H0248900.PDFJandy Lite2 LJ Heater I/O Manual2.45 MB
 
Close

Product Comparison

 
 
Close

 
Share